"NetID"
Here you can set the network ID of the connected PRP network. The valid value range is 1 to
6.
The NetID is used to distinguish between frames from different redundant PRP networks in
an HSR ring. It is not relevant in "HSR SAN Mode".
"Duplicate Aging Time"
The default value from the HSR standard is 400 ms. This value cannot be changed.
"Limitation" / "Max Throughput"
By selecting the "Limitation Enabled" check box, the data throughput from the interlinks to the
HSR ports is limited to the set value. The limitation can be specified with "Max Throughput".
A limitation between 50% and 80% is possible. If the load on the interlinks is greater than the
value set, frames are discarded. This occurs regardless of Ethertypes and any VLAN priorities.
7.8.4

Fault Mask

Function of the "X200 Fault Mask Power" dialog box
With the "X200 Fault Mask Power" dialog box, you specify the fault/error states to be monitored
by the SCALANCE X-200RNA and that will trigger the signaling contact. Possible fault/error
states are the absence of the power supply, power supply too low, or an interrupted connection
or an unexpected connection established to a partner device. If the signaling contact is
triggered, this causes the fault LED on the device to light up and, depending on the
configuration of the event table, can trigger a trap or an entry in the log table.
Device-related link monitoring of the ports
A SCALANCE X-200RNA provides device-related link monitoring. A link-up or link-down also
affects the message system if the SCALANCE X-200RNA was appropriately configured.
Setting of the "X200 Fault Mask Power" dialog box on the device
Optionally, the dialog box can be set using the SELECT/SET button on the SCALANCE
X-200RNA. For more detailed information, refer to the section "SELECT/SET button
(Page 46)".