Error Codes - Mitsubishi A1SJ61BT11 User Manual

Control & communication link system master/local module, melsec a
Table of Contents

Advertisement

13 TROUBLESHOOTING

13.3 Error Codes

Error code
Error details
(hexadecimal)
7000 to
(Errors detected by serial
7FFF
communication module, etc)
B104
Data link restart error
B105
Data link stop error
Transient data can not be
B110
1
received
Transient data receiving order
B111
1
error
B112
1
Transient data length error
B113
1
Transient data ID error
B115
1
Link error
B116
1
Packet error
Corresponding station error
B201
1
during sending
B205
Transient target station error
Processing request error during
B301
link stop
Specified station number
B302
setting error
Specified station number not
B303
set error
B304
Line test error station detected
Specified station number
B306
setting error
B307
All stations data link error
Station number setting error
B308
(installation status)
B309
Station number overlap error
1: Error code added to the function version B or later.
Table 13.1 lists the error codes that are stored in the link special registers (SW).
When the standby master station is operating as the master station, the detectability is
identical to that of the master station.
When the standby master is operating as a local station, the detectability is identical to
that of the local station.
Table 13.1 Error code list (1/6)
Cause of error occurrence (details)
———
Data link restart (SB0000) was executed
for the station that was performing a data
link.
Data link stop (SB0002) was executed
for the station that had stopped a data
link.
A line error has occurred.
A line error has occurred.
A line error has occurred.
A line error has occurred or an
instantaneous power failure has occurred
at the send station.
A line error has occurred.
A line error has occurred.
A data link error occurred at the
corresponding station during transient
transmission.
A transient request was issued to other
than the intelligent device station.
Line test request was issued while the
link was stopped.
The specified station number exceeded
the highest communication station
number during temporary error invalid
request/temporary error invalid cancel
request.
The station number was not specified during
temporary error invalid request/temporary
error invalid cancel request.
An error was detected in a remote
station, intelligent device station or
standby master station when a line test
was performed.
A station number other than the head
station number was specified during
temporary error invalid request/temporary
error invalid cancel request.
All stations were in data link error status
when one of the following requests was
made:
• SB0000 (data link restart)
• SB0002 (data link stop)
The station number of the slave station is
outside of the range between "1 and 64".
The station number of the connected
module was duplicated (including
number of occupied stations).
However, this excludes the duplicate
head station number.
Corrective action
Handle by referring to the
troubleshooting section of the Serial
Communication Module User's
manual.
Execute Data link restart (SB0000)
for the station that has stopped a
data link with Data link stop
(SB0002).
Execute Data link stop (SB0002) for
the station that is performing a data
link.
Check the line.
Check the line.
Check the line.
Check the line, or check the supply
power and power supply module of
the send station.
Check the line.
Check the line.
Check the communication status of
other stations, whether or not a
temporary error invalid station is
specified, or if the corresponding
station is stopped.
Check the target station.
Perform a line test while the link is
being established.
Specify a station number that is no
greater than the highest
communication station number.
Set a specified station number.
(SW0003, SW0004 to SW0007)
Check that the remote station,
intelligent device station or standby
master station is operational and
that the cable is not disconnected.
Specify a head station when
temporary error invalid
request/temporary error invalid
cancel request is requested.
Request again after the data link
becomes normal.
Set the station number of the slave
station within the range between "1
and 64".
Check the module station number.
13 - 6
MELSEC-A
Detectability
Master station
Local station