8 PROGRAMMING
Number
Name
Communication command
SB0030 2
(1) acceptance
Communication command
SB0031 2
(1) complete
Communication command
SB0032 2
(2) acceptance
Communication command
SB0033 2
(2) complete
Data link restart
SB0040
acceptance
SB0041
Data link restart complete
Master station switch data
SB0042 1
link start acceptance
Master station switch data
SB0043 1
link start complete
SB0044
Data link stop acceptance
SB0045
Data link stop complete
Temporary error invalid
SB0048 1
station acceptance
Temporary error invalid
SB0049 1
station complete status
Temporary error invalid
SB004A 1
station canceling
acceptance status
1: Link special relay added to the function version B or later
2: Link special relay added to the software version J (manufactured in Jan., 1998)or later
Indicates the acceptance status of SEND/RECV/READ/WRITE/REQ
commands (when channel 1 is used).(Usable on AJ61QBT11 and
A1SJ61QBT11)
OFF : Not accepted
ON : Accepted
Indicates the complete status of SEND/RECV/READ/WRITE/REQ
commands (when channel 1 is used). (Usable on AJ61QBT11 and
A1SJ61QBT11)
OFF : Not completed
ON : Completed
Indicates the acceptance status of SEND/RECV/READ/WRITE/REQ
commands (when channel 2 is used). (Usable on AJ61QBT11 and
A1SJ61QBT11)
OFF : Not accepted
ON : Accepted
Indicates the complete status of SEND/RECV/READ/WRITE/REQ
commands (when channel 2 is used). (Usable on AJ61QBT11 and
A1SJ61QBT11)
OFF : Not completed
ON : Completed
Indicates data link restart specification acceptance status.
OFF : Not accepted
ON : Startup specification accepted
Indicates data link restart specification acceptance complete status.
OFF : Not complete
ON : Startup complete
Indicates the acceptance status of data link start switch command
from the standby master station to the master station (Usable on the
standby master station).
OFF : Not accepted
ON : Accepted
Indicates the acceptance status of data link start switch command
from the standby master station to the master station (Usable on the
standby master station).
OFF : Not completed
ON : Completed
Indicates data link stop specification acceptance status.
OFF : Not accepted
ON : Stop specification accepted
Indicates data link stop specification acceptance complete status.
OFF : Not complete
ON : Stop complete
Indicates the acceptance status of the temporary error invalid station
request command.
OFF : Not accepted
ON : Accepted
Indicates the acceptance complete status of the temporary error
invalid station request instruction.
OFF : Not executed
ON : Temporary error invalid station confirmed
Indicates the acceptance status of the temporary error invalid station
canceling request instruction.
OFF : Not executed
ON : Instruction accepted
8 - 13
Description
MELSEC-A
Availability
(
: available,
: not available )
Online
Offline
Master
Local
station
station