3 SPECIFICATION
3.5 Buffer Memory

3.5.1 Buffer memory list

Address
Hex.
Dec.
0
to 5F
0 to 95
H
H
60
to 7F
96 to 127
H
H
80
to CD
128 to 205
H
H
CE
to DF
206 to 223
H
H
E0
to 15F
224 to 351
H
H
160
to 1DF
352 to 479
H
H
1E0
to 2DF
480 to 735
H
H
2E0
to 3DF
736 to 991
H
H
3E0
to 5DF
992 to 1503
H
H
5E0
to 5FF
1504 to 1535 Link special relay (SB) Stores the data-link status.
H
H
600
to 7FF
1536 to 2047
H
H
800
to 9FF
2048 to 2559
H
H
A00
to FFF
2560 to 4095 Random access buffer
H
H
Do not write to areas that are prohibited to use. An error may occur.
The buffer memory is used to swap data between the master/local module and the PC
CPU.
In the PC CPU, the FROM/TO instructions are used to read/write data.
The contents of the buffer memory return to the default values when the power is
turned off and the PC CPU is reset.
The buffer memory list is shown in Table 3.4.
Table 3.4 (1) Buffer memory list (bank 0)
Item
Parameter information
Stores the information (parameters) to
area
execute the data link.
(Prohibited to use)
Parameter information
Stores the information (parameters) to
area
execute the data link.
(Prohibited to use)
When master station: Stores the input
status from the remote/local station.
Remote input (RX)
When local station: stores the input status
from the master station.
When master station: Stores the output
status of the output to the remote/local
station.
Remote output (RY)
When local station: Stores the output status
of the output to the master station.
When master station: Stores the
transmission data to the remote/all local
Remote register (RWw)
stations.
(Master station: for
sending
When local station: Stores the transmission
Local station: for
data to the master/other local stations.
sending/receiving)
Also, stores the received data from the
remote/other local stations.
Remote register (RWr)
When master station: Stores the received
(Master station: for
data from the remote/local station.
receiving
When local station: Stores the received
Local station: for
data from the master station.
receiving)
(Prohibited to use)
Link special register
Stores the data-link status.
(SW)
(Prohibited to use)
Uses for dedicated instruction of RIRD,
RIWT, etc.
Details
3 - 18
MELSEC-A
Availability
Read/write
Master
Local
possibility
station
station
Read/write
enabled
Read/write
enabled
Read only
Write only
Read/write
enabled
Write only
Read/write
enabled
Write only
Read/write
enabled
(write
disabled
depending
on the
device)
Read/write
enabled
: Usable
: Prohibited to use