Station Number Overlap Checking Function - Mitsubishi A1SJ61BT11 User Manual

Control & communication link system master/local module, melsec a
Table of Contents

Advertisement

4 FUNCTIONS

4.12.3 Station number overlap checking function

(Example)
Local station (station number 1, occupied stations: 4)
Remote device station (station number 4, occupied stations: 2)
(Example)
Local station (station number 1, occupied stations: 4)
Remote device station (station number 1, occupied stations: 2)
Checks whether the number of occupied stations overlap, by observing the status of
the stations actually connected during data link startup (turn on Yn6 and Yn8).
However, if the starting head number overlaps, this would not be a part of the overlap
checking.
(1) When there is an overlap, the "M/S" LED flashes, and the overlap status is stored
in SW0098 to SW009B.
(2) Even if overlap exists, data link can be continued with other normally functioning
stations.
(3) By correcting the switch setting to the normal status and starting up the data link
(turn on Yn6 and Yn8) again, the "M/S" LED is turned off and the data in SW0098
to SW009B are cleared.
Station 1 Station 2 Station 3 Station 4
Station 1 Station 2 Station 3 Station 4
Head
Overlap
Station 1 Station 2
4 - 30
MELSEC-A
Overlap
Station 4 Station 5