Levelflex FMP56, FMP57 FOUNDATION Fieldbus
Operating time
Navigation
Description
User interface
Additional information
Last backup
Navigation
Description
User interface
Configuration management
Navigation
Description
Selection
Factory setting
Endress+Hauser
"Configuration backup display" submenu
This submenu is only visible if a display module is connected to the device.
The configuration of the device can be saved to the display module at a certain point of
time (backup). The saved configurateion can be restored to the device if required, e.g. in
order to bring the device back into a defined state. The configuration can also be
transferred to a different device of the same type using the display module.
Navigation
Setup → Advanced setup → Conf.backup disp
Setup → Advanced setup → Conf.backup disp → Operating time
Indicates how long the device has been in operation.
Days (d), hours (h), minutes (m), seconds (s)
Maximum time
9 999 d ( ≈ 27 years)
Setup → Advanced setup → Conf.backup disp → Last backup
Indicates when the last data backup was saved to the display module.
Days (d), hours (h), minutes (m), seconds (s)
Setup → Advanced setup → Conf.backup disp → Config. managem.
Select action for managing the device data in the display module.
• Cancel
• Execute backup
• Restore
• Duplicate
• Compare
• Clear backup data
• Display incompatible
Cancel