Activate Transmission Device; Detector Removal; Change Device On V.24 Interface - Bosch MPC-xxxx-C Series User Manual

Panel controller
Hide thumbs Also See for MPC-xxxx-C Series:
Table of Contents

Advertisement

Panel Controller
5.
6.
7.
Notice!
In the HVAC element category, the Auto function field is also offered. Select this function
field to assign automatic mode to a fan, for instance.
15.4

Activate Transmission Device

To activate a transmission device:
1.
2.
3.
4.
To end activation of the selected elements:
1.
2.
3.
4.
15.5

Detector removal

Notice!
To remove a detector, all acoustic signals and transmission devices are bypassed for 15
minutes. They are automatically un-bypassed when the 15 minutes are up.
The acoustic signals can also be manually un-bypassed before the specified time has elapsed.
To remove a detector:
1.
2.
3.
To switch the signaling devices back on before the 15 minutes are up:
4
When the 15 minutes are up, the panel emits a brief signal tone and the start menu is
displayed.
15.6

Change device on V.24 Interface

On the V.24 interface, other devices can be optionally assigned in addition to a permanently
assigned device.
Bosch Sicherheitssysteme GmbH
Select On to activate the selected notification appliances.
The selected signaling devices are activated.
Select All to activate all notification appliances.
To end activation of the selected elements, repeat the same steps but select Off in step
5.
In the start menu, select Maintenance
Activate transmission device
A list of the elements is displayed. Refer to Working with lists, page 26 for information on
how to navigate through a list.
Select the required list fields.
The list fields are marked.
Select On.
The selected transmission devices are activated:
In the start menu, select Maintenance
Activate transmission device
Select the list fields of the activated transmission devices.
Select Off.
The transmission devices are no longer activated.
In the start menu, select Maintenance
Remove detector
Select OK to confirm the request. All signaling and transmission devices will be
inoperative for 15 minutes. The counter then counts from 15 minutes to zero minutes.
The detectors can be removed during this time.
Select Restore manually disabled outputs.
User Guide
Maintenance | en
71
2017.09 | 7.0 | F.01U.258.929

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fpa-1200-mpc-c

Table of Contents