Alarm Message To The Panel; Optical And Acoustic Signals; Displaying The Detector Zones In Alarm State - Bosch MPC-xxxx-C Series User Manual

Panel controller
Hide thumbs Also See for MPC-xxxx-C Series:
Table of Contents

Advertisement

42
en | Alarm
Day mode
Notice!
Depending on the security level in question, not all detectors can be switched to day mode.
Depending on the configuration, a distinction is made between the following possible alarm
delays in day mode:
9.4

Alarm message to the panel

The following description has been written on the basis of a sample fire alarm message.
9.4.1

Optical and acoustic signals

If the transmission device to the fire department is activated, the "Transmission Device
activated" signal light lights up red.
9.4.2

Displaying the detector zones in alarm state

The number of messages in question is displayed on the status bar.
Notice!
First of all, the logical zones in which one or more detectors have triggered an alarm are
listed. To display the individual detectors, select the logical zone you require. See also
Displaying the individual detectors in a logical zone, page 44.
The individual messages are shown in the display:
Logical Zones
Notice!
A maximum of four alarm messages can be displayed on the display simultaneously. Only
fields that can be operated are displayed (e.g. Acknowledge and Reset).
2017.09 | 7.0 | F.01U.258.929
Alarm verification
Pre-alarm
A pre-alarm is displayed for the following alarm delays:
Intermediate alarm storage
Dual-detector dependency
Dual-zone dependency
For a detailed description of the various alarm delays, see Entry delays, page 40.
Internal alarm
An alarm that is reported to the panel in day mode. No transmission devices to the fire
department are activated.
The red alarm signal light on the LED display lights up.
An internal buzzer sounds; see also Switching off internal buzzer, page 46.
Depending on the configuration, sounders and/or visual notification appliances (e.g.
sirens, strobes) are activated.
List fields with black background: unacknowledged alarm messages
List fields without distinction: acknowledged alarm messages
User Guide
Panel Controller