9410 series
Configuring SNMP using ION Setup
70
NOTE: You should only configure the variable name and description. Changing other
fields in your MIB file may cause the client software to report problems or return errors
when trying to retrieve or view parameters.
The variable name must conform to the following rules:
The first character must be a letter.
The first character must be lower case.
The name must not contain any special characters such as *, ?, &.
The name must not contain spaces.
1. Open your meter's MIB file in a text editing program (such as Notepad).
2. Update the variable name and description so they match the meter values
connected to the SNMP Mapping module.
3. Save your meter's MIB file. Make sure you keep the original file extension of .MIB.
This example shows an original and an updated OID entry in an MIB file, where the
default meter value of voltage line-to-neutral phase A is modified in the meter's SNMP
Mapping module and is now connected to voltage line-toneutral phase C.
Original OID entry
Vln_a OBJECT-TYPE
SYNTAX DisplayString (SIZE (0. . 255))
ACCESS read-only
STATUS mandatory
DESCRIPTION "Host Meter Voltage Line A to Neutral Units = V (Volts)" ::= { Siemens Industry 34 }
You must update the variable name and description to match the meter values
connected to the SNMP Mapping module:
Value
Variable name
Description
The SNMP client software reads the original and updated file as follows:
Original
variable name: Vln_a
Description: "SNM1 Input 1 - Voltage (line-
toneutral) phase A"
You can enable SNMP and configure SNMP trapping using ION Setup.
You must download the ION MIB file from www.usa.siemens.com/pds
1. Start ION Setup.
2. Open the Setup Assistant for your meter.
3. Navigate to Communications > Network Settingsand select the SNMP tab.
Original
Vin_a
"Host Meter Voltage Line A to
Neutral Units = V (Volts)" ::= {
Siemens Industry 34 }
Updated
variable name: Vln_c
Description: "SNM1 Input 1 - Voltage (line-to-
neutral) phase C"
Communications
Updated
Vin_c
Host Meter Voltage Line C to
Neutral Units = V (Volts)" ::= {
Siemens Industry 34 }