Default waveform recording configuration
Configuring waveform recording using ION Setup
108
Related Topics
Setpoint learning overview
COMTRADE
Minimum configuration requirements for basic metering
Your meter's waveform recording operates once your nominal values are configured.
Your meter has the following default waveform recorders:
Waveform recorder
Wfm Rc V1-Sg/Sw
Wfm Rc V2-Sg/Sw
Wfm Rc V3-Sg/Sw
Wfm Rc I1-Sg/Sw
Wfm Rc I2-Sg/Sw
Wfm Rc I3-Sg/Sw
You can configure waveform recording using ION Setup.
For waveform recording to trigger automatically, you must enter your system's nominal
(normal) voltage and current values, and then the amount of deviation from the
nominal required to trigger waveform recording.
Changing your meter's waveform recording configuration clears your meter's existing
waveform records.
DATA LOSS
Failure to follow these instructions can result in equipment damage.
Ensure that all important data has been recorded before configuring waveform
recording.
1. Start ION Setup.
2. Open the Setup Assistant for your meter.
3. Navigate to Alarming and click the Sag/Swell tab. Configure your meter's sag/
swell detection parameters.
Description
V1 voltage waveforms recorded during a defined sag or swell event.
V2 voltage waveforms recorded during a defined sag or swell event.
V3 voltage waveforms recorded during a defined sag or swell event.
I1 current waveforms recorded during a defined sag or swell event.
I2 current waveforms recorded during a defined sag or swell event.
I3 current waveforms recorded during a defined sag or swell event.
NOTICE
Logging
7EN05-0336-01