Communications

FTP

FTP memory allocation
FTP file structure and permissions
7EN05-0336-01
4. Select the General tab and configure the site.
Parameter
Name
Comm Link
Ethernet options
Gateway Info: IP Addr
Gateway Info: Port
5. Click OK to create the site.
6. Right-click on your newly created site and select Insert Item.
The New Network Item dialog appears.
7. Make sure your newly created Ethernet gateway site is selected in Attach to.
8. Select Device and click OK.
The New Device dialog appears.
9. Enter the details of your serial device. Click OK to add the serial device to your
Ethernet gateway site.
10.Repeat for all the serial devices on the gateway meter.
NOTE: Use a separate standard Ethernet connection in ION Setup to connect to
and read data from your Ethernet gateway meter.
Your meter has an internal FTP server that you can use to load files, such as custom
webpages, and upgrade your meter and meter accessories.
File transfer protocol (FTP) is a standard, client-server network protocol used to
transfer files over TCP (Ethernet) networks.
Your meter's FTP memory usage changes when you copy a file to the meter's internal
FTP site or modify a feature that uses the meter's FTP site.
If you attempt to load a file onto your meter's FTP site that is too large, your FTP
program displays an error, and you must delete files from your meter's internal FTP
site to free up memory before loading the file.
If you modify a meter feature which uses FTP memory, such as increasing the number
of COMTRADE waveform records, the meter checks to confirm sufficient space is
available on its internal FTP site before enabling the modified feature. If there is
insufficient space, the feature is disabled, and you must delete files from your meter's
FTP site to increase the available space before enabling the feature.
Your meter has an FTP folder structure.
COMTRADE: you can read COMTRADE files from these folders, but you cannot
delete or add files to these folders.
IEC61850: you can add an IEC 61850 configuration (CID) file to this folder to
activate the IEC 61850 protocol functions of your meter.
Values/Options
-
Ethernet
Gateway
7801, 502
9410 series
Description
Ethernet gateway site name
Ethernet communications
Ethernet gateway
communications
IP address of the Ethernet
gateway meter
7801 for EtherGate
502 for Modbus gateway
65