Siemens 9410RC User Manual page 104

9410 series
Table of Contents

Advertisement

9410 series
Energy/Demand log
Sag/swell log
EN50160 compliance logs
104
Harm Mean Log
V1 THD mean
I1 K Fac mean
V2 THD mean
I2 K Fac mean
V3 THD mean
I3 K Fac mean
I1 THD mean
I2 THD mean
I3 THD mean
The Energy/Demand log records energy and demand data used by energy
management software to generate reports. Changing the logged data can prevent the
generation of reports that use this data.
The Sag/swell Log provides details of power quality events. By default, it logs the
following values:
SS1 DistDur
SS1 DistV1Min
SS1 DistV1Engy
SS1 DistV2Min
SS1 DistV2Engy
SS1 DistV3Min
SS1 DistV3Engy
SS1 DistNominal
The EN50160 compliance logs are used to record EN50160 compliance parameters:
Data recorder
EN50160 component
logged
Power frequency and
EN50160 Frq/Mg
supply magnitude
EN50160 Hrm Vlt
Harmonics
EN50160 Intrp
Short/log interruptions
EN50160 Ovrvlt1
Temporary overvoltage
EN50160 Ovrvlt2
EN50160 Prm-f/V
Parameter data
(disabled by default)
EN50160 Prm-VIr
EN50160 Vunbal
Voltage unbalance
The meter logs EN50160 counter data for present and previous observation periods as
well as EN51060 events.
See the EN50160 2010 compliance and ION meters technical note, available from
www.usa.siemens.com/pds, for more information about your meter's EN50160
compliance.
Harm High Log
V1 THD high
I1 K Fac high
V2 THD high
I2 K Fac high
V3 THD high
I3 K Fac high
I1 THD high
I2 THD high
I3 THD high
SS1 DistV1Max
SS1 DistV1Avg
SS1 DistV2Max
SS1 DistV2Avg
SS1 DistV3Max
SS1 DistV3Avg
SS1 Swell Lim
SS1 Sag Lim
Data recorder
EN50160 component
logged
EN50160 PrmHrm1
Parameter data
(disabled by default)
EN50160 PrmHrm2
EN50160 Vlt Dp1
EN50160 Vlt Dp2
EN50160 Vlt Dp3
Supply voltage dips
EN50160 Vlt Dp4
EN50160 Vlt Dp5
Logging