Battery Settings; Maintenance; Personalisation Using External Software - Eaton MX Frame 15000 RT Installation And User Manual

Pulsar series
Table of Contents

Advertisement

Battery settings

Function
Auto Battery Test
Low Batt Warning
User Batt Settings
Deep Disch Protect

Maintenance

Function
Model
Measurement
Alarm History
System Diagnosis
Manual Batt Test
Led & Buzzer Test
Life Cycle Monitoring
Statistics
Operation Limits

Personalisation using external software

Insert the Solution-Pac CD-ROM in the drive.
On the first navigation screen, select "Point to Point solution" and follow the instructions on how to install the
Personal Solution-Pac software.
Then select "Settings", "Advanced settings" and "UPS settings".
Note that only the Windows versions of the Personal Solution-Pac software offer this possibility.
4. Access to measurements and personalisation data
Factory setting
Everyweek
20%
UPS reads number of
battery modules
connected
Yes
Sub-Function
Power Module
Frame
Monitoring by selecting
modules 1 trough 4
Read
Erase
Module detection
Manual Battery Test
Led & Buzzer Test
LCM
Auto Statistics
Custom Statistics
Operation Limits
Options
Comments
No test / everyday /
everyweek /everymonth
0 to 100%
1% increment
From 0 to 40 Ah
5 Ah increment
No
Protection against deep discharge.
If disable, EATON warranty will be
void
Option / Display
Comments
SN: xxxxxxxxx
Serial number
SOFT: xxx
Soft version
NT: xxx
Technical level
Status for each module:
Input/Output
kVA to load Battery
capacity
Description
10 alarms can be stored
Date Hour
automatically
Alarm xxx
No / Yes
Status for each module
No / Yes
No / Yes
Enable / Disable
Life cycling monitoring alarms
Statistics
Reset Date ?
Are you sure ?
Automatic alarms displayed when
UPS is operating near the limits
34008486EN/AC - Page 33

Advertisement

Table of Contents
loading

This manual is also suitable for:

Mx frame 20000 rt

Table of Contents