2. AC Wiring and front selector

3-phase diagram:

When used to measure a PV Inverter, terminals 1, 4 and 7 should face the PV inverter to ensure
correct direction of current and power.
single phase single function diagram:
Note the jumper between terminals 1 and 4. You do not need this connection if you have the version
AV2 of the sensor:
The diagram shows the wiring when used as a grid meter.
To measure a single phase PV inverter in a 3-phase system, connect all 3 phases to the grid phasing
terminals (3, 6 and 9). Now you can chose on which phase you want the PV inverter by connecting the
L1 line of the PV inverter to terminal 1, 4 or 7.
single phase dual function diagram:
In this diagram, a single meter is used to both measure the grid and a single phase PV Inverter.