4. SETUP AND PREPARATION BEFORE OPERATION
4.2

Name of Each Part

The name of each part in the AJ65BT-64DAV/DAI is described.
Number
Name
Station number
1
setting switch
B RATE (Transfer
2
baud rate) setup
switch
CH. (CHANNEL)
3
selection switch
OFFSET/GAIN
4
(Offset/gain)
setting switch
UP/DOWN switch
5
RESET switch
6
MITSUBISHI
MELSEC
AJ65BT-64DA
↓ ×10
The AJ65BT-64DAV/DAI station number
↓ ×1
is set within the range 1 to 63. (Factory shipment setting : 00)
Setting number
0
1
2
3
4
Unused (When a value other than 0 to 4 is set, L ERR. LED turns on, and results in a
communication error.)
Select the channel to perform offset adjustment or gain adjustment.
(Positions other than 1 to 4 are not processed.)
The switch to set the offset/gain values during test mode.
(1) OFFSET position
: Calibration mode for the offset value
(2) GAIN position
: Calibration mode for gain value
(3) SET position
: When the switch is set from the OFFSET/GAIN position,
The switch to adjust the analog output value for the offset/gain of the specified
channel.
The analog output value increases/decreases by turning on the UP/DOWN
switch.
Resets the H/W.
Initializes the AJ65-BT-64DAV/DAI I/O signals, remote register, and operation
processing.
When the switch is turned on, AJ65BT-64DAV/DAI initial data
processing request flag turns on.
4-2
B RATE
STATION NO.
X10
X1
0 1
0 1
0 1
9
2
2
8
2
PW
3
3
7
3
4
6
4
6
4
RUN
5
5
L RUN
CH.
OFFSET GAIN. RESET
SD
RD
1
SET
2
L ERR.
3
4
GAIN
DOWN
Description
Transfer baud rate
156kbps(Factory shipment setting)
625kbps
2.5Mbps
5Mbps
10Mbps
which are modes to record offset/gain value to the SET
position, to the SET position, the offset/gain value is
recorded.
MELSEC-A
4