3. SPECIFICATIONS
3.5

I/O Signals to the Master Station

Assignment of the I/O signals and function of each signal are explained.
3.5.1
The AJ65BT-64DAV/DAI uses 32 input points and 32 output points for exchanging signals with the
master station.
An RX device indicates an input signal from the AJ65BT-64DAV/DAI to the master module, and a RY
device indicates an output signal from the master module to the AJ65BT-64DAV/DAI.
Device No.
RXn0
to
RXnF
RX (n+1) 0
to
RX (n+1) 7
RX (n+1) 8
RX (n+1) 9
RX (n+1) A
RX (n+1) B
RX (n+1) C
RX (n+1) D
RX (n+1) E
RX (n+1) F
Point
If a device not allowed to use is turned on/off from the sequence program, the function of the
AJ65BT-64DAV/DAI is not guaranteed.

I/O signal list

1
*
The allocation of the I/O signals and the name of each signal are listed in Table 3.4.
Signal direction:
AJ65BT-64DAV/DAI→Master
Signal name
Unusable
Unusable
Initial data processing request
flag
Initial data setting complete flag
Error status flag
Remote READY
Unusable
Unusable
(Unusable: QnA)
(Unusable: QnA)
n: The address allocated to the master station in the station number setting
*1 Although the number of occupied stations for the AJ65BT-64DAV/DAI is
2, inputs, RX(n+2) 0 to RX(n+3)F, are not used.
However, devices for inputs, RX(n+2) 0 to RX(n+3)F, and outputs,
RY(n+2) 0 to RY(n+3) F, are reserved in the master module or CPU
module. When creating a program, pay attention to device allocation.
Table 3.4 I/O signals
Master→AJ65BT-64DAV/DAI
Device No.
RYn0
RYn1
RYn2
RYn3
RYn4
RYn5
to
RYnF
RY (n+1) 0
to
RY (n+1) 7
RY (n+1) 8
RY (n+1) 9
RY (n+1) A
RY (n+1) B
RY (n+1) C
RY (n+1) D
RY (n+1) E
RY (n+1) F
3-10
MELSEC-A
Signal direction:
Signal name
CH.1 analog output permission
signal
CH.2 analog output permission
signal
CH.3 analog output permission
signal
CH.4 analog output permission
signal
Offset/gain value selection
Unusable
Unusable
Initial data processing complete
flag
Initial data setting request flag
Error reset request flag
Unusable
Unusable
Unusable
(Unusable: QnA)
(Unusable: QnA)