ABB REG670 Product Manual page 76

Relion 670 series, generator protection
Hide thumbs Also See for REG670:
Table of Contents

Advertisement

Generator protection REG670 2.2 and Injection equipment REX060,
REX061, REX062
Product version: 2.2.1
Table 63. Negative sequence time overcurrent protection for machines NS2PTOC
Function
Operate current, step 1 - 2
Reset ratio
Operate time, start at 0 to 2 x I
Reset time, start at 2 x I
to 0
set
Operate time, start at 0 to 10 x I
Reset time, start at 10 x I
to 0
set
Time characteristics
Inverse time characteristic, step 1 - 2
2
=
I t
K
2
Reset time, inverse characteristic,
step 1 - 2
2
=
I t
K
2
Minimum operate time for inverse
time characteristic, step 1 - 2
Maximum trip delay at 0.5 x I
I
, step 1 - 2
set
Independent time delay at 0.5 x I
2 x I
, step 1 - 2
set
Independent time delay for Alarm at
0.5 x I
to 2 x I
set
set
76
GUID-E5718F80-556D-4852-A8F2-90E0F578D763 v9
Range or value
(3-500)% of
IBase
>95%
Min. = 15 ms
set
Max. = 30 ms
Min. = 15 ms
Max. = 30 ms
Min. = 5 ms
set
Max. = 20 ms
Min. = 20 ms
Max. = 35 ms
Definite or Inverse
K=1.0-99.0
Reset Multiplier = 0.01-20.00
(0.000-60.000) s
to 2 x
(0.00-6000.00) s
set
to
(0.00-6000.00) s
set
(0.00-6000.00) s
Accuracy
±1.0% of I
at I ≤ I
r
r
±1.0% of I at I > I
r
-
-
-
-
-
-
±2.0% or ±40 ms whichever is greater
±5.0% or ±40 ms whichever is greater
±0.2% or ±35 ms whichever is greater
±0.2% or ±35 ms whichever is greater
±0.2% or ±35 ms whichever is greater
±0.2% or ±35 ms whichever is greater
1MRK 502 074-BEN A
ABB