Generator protection REG670 2.2 and Injection equipment REX060,
REX061, REX062
Product version: 2.2.1
Table 24. Auxiliary DC supply voltage influence on functionality during operation
Dependence on
Ripple, in DC auxiliary voltage
Operative range
Auxiliary voltage dependence, operate
value
Interrupted auxiliary DC voltage
Interruption
interval
0–50 ms
0–∞ s
Restart time
Table 25. Frequency influence (reference standard: IEC 60255–1)
Dependence on
Frequency dependence, operate value
Frequency dependence for distance protection operate value
Harmonic frequency dependence (20% content)
Harmonic frequency dependence for distance protection (10%
content)
Harmonic frequency dependence for high impedance differential
protection (10% content)
Harmonic frequency dependence for overcurrent protection
Type tests according to standards
ABB
Reference value
Within nominal
range
max. 2%
15% of EL
Full wave rectified
±20% of EL
24-60 V DC ± 20%
100-250 V DC ±20%
Within nominal range
f
r
f
r
f
r
f
r
2
2nd, 3rd and 5
2
2
M16706-1 v10
Influence
0.01%/%
0.01%/%
No restart
Correct behaviour at power down
< 300 s
±2.5 Hz for 50 Hz
±3.0 Hz for 60 Hz
±2.5 Hz for 50 Hz
±3.0 Hz for 60 Hz
nd
rd
th
, 3
and 5
harmonic of f
r
th
harmonic of f
r
nd
th
, 3rd and 5
harmonic of f
r
nd
rd
th
, 3
and 5
harmonic of f
r
1MRK 502 074-BEN A
Influence
±1.0%/Hz
±2.0%/Hz
±2.0%
±10.0%
±10.0%
±3.0%
IP15778-1 v1