seconds before the Event will clear and reset. Clear Delay can be up to 14400
seconds (4 hours).
g. Type in the desired Trip Delay time in seconds. Any value other than "0" means
that the measurement must exceed the threshold for this many seconds before the
Event will be tripped. Trip Delay can be up to 14400 seconds (4 hours).
h. Latching Mode: If enabled, this Event and its associated Actions (see below)
remain active until the Event is acknowledged, even if the measurement
subsequently returns to normal.
i. Valid Time: Allows user to set specific times an Event will trigger a notification.
Multiple Valid Time entries can be set allowing users to set alerts to notify different
Targets based on time of day or day of week.
j. To determine where the alert notifications will be sent to when this particular Alarm
or Warning Event occurs, click the Add icon to create a new Action, then select the
desired options from the drop-down menu:
Figure 3-9 Add Page
· Target: is the email address or SNMP manager to which notifications should be sent
when the Event is tripped.
GM1118 Watchdog 100 Instruction Manual
NOTE
Target Delays and Repeats are shared across all alarms. If
multiple Delay and/or Repeat values are needed for specific
Targets, each one must be added to the Target list and then the
appropriate 'Enabled' box checked on each alarm. See screen-
shot below for example.