Chapter 3 - Setup
29
Figure 3-4 Deleting a Sensor
Relay Control
Relay Contact Ratings
The output relay contacts are intended to carry low voltage signals only. Do
not exceed the following ratings on the output relay contacts:
DC: 60V, 30W
AC: 30Vrms, 1 A
Relay Configuration
The Watchdog 100 units provide one output relay that can be operated
remotely or set to automatically open or closed based on alarm conditions. A
relay in non-latching mode will automatically energize and de-energize as its
associated alarms trip and clear. A relay in latching mode will similarly energize
on an alarm trip, but will only de-energize when acknowledged by the user on
the
Alarms and Warning
page. See
Add/Modify Alarms and Warnings
for
additional information on associating an alarm condition with the output relay.
Relay Labeling and Mode Select
The relay label and manual override or alarm mode can be changed on the
Configuration page.
GM1118 Watchdog 100 Instruction Manual