ESIE15-11A
|
Part 3. Field settings

3.2. Field settings, specific for BRC1D51/52

Mode
FIRST
No.
CODE
Description of setting
Note 1
NO.
10(20)
0
Filter Contamination - Heavy/Light
(Setting for spacing time of display
time to clean air filter) (Setting for
when filter contamination is heavy,
and spacing time of display time to
clean air filter is to be halved)
1
Long-life filter type (setting of filter sign indication
time). (Change setting when ultra-long filter is
installed)
2
Thermostat sensor in remote controller
3
Spacing time of display time to clean air filter
count (setting for when the filter sign is not to be
displayed)
12(22)
1
ON/OFF input from outside (setting for when
forced ON/OFF is to be operated from outside).
2
Thermostat differential changeover (setting for
when using remote sensor).
13(23)
0
High air outlet velocity (for high ceiling applica-
tions).
1
Selection of air flow direction (setting for when a
blocking pad kit has been installed).
3
Selection of air flow function (setting for when
using a decoration panel for outlet).
4
Air flow direction range setting.
6
Setting the external static pressure (setting
according to the connected duct resistance)
(for FHYK, follow the high ceiling setting)
15(25)
3
Drain pump operation with humidifying.
1b
0
Permission level setting
1
Leave home function
2
Thermostat sensor in remote controller (for limit
operation and leave home function only)
Page 28
VRV4 indoor units
SECOND CODE NO. Note 2
01
Ultra long
Approx.
life filter
10.000
hrs.
Long life
Approx.
filter
2.500
hrs.
Standard
Approx.
filter
200 hrs.
Long-life
filter
Use
Display
Forced OFF
1°C
≤2,7 m
4-way flow
Equipped
Upper
Normal
(Normal)
Equipped
Level 2
Not
permitted
Use
3. Wired remote controller BRC1D51/52
02
03
Approx.
-
5.000
hrs.
Approx.
1.250
hrs.
Approx.
100 hrs.
Ultra-long
-
life filter
Not use
-
Do not
-
display
ON/OFF
-
operation
0,5°C
-
>2,7≤3,0 m
>3,0≤3,5 m
3-way flow
2-way flow
Not
-
equipped
Normal
Lower
High static
Low static
pressure
pressure
(High
-
ceiling)
Not
-
equipped
Level 3
-
Permitted
-
Not use
-
04
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
23/09/16