Smart Start-Up With Basic Program Group Parameters - Allen-Bradley PowerFlex 523 Quick Start Manual

Powerflex 520-series adjustable frequency ac drive
Hide thumbs Also See for PowerFlex 523:
Table of Contents

Advertisement

PowerFlex 520-Series Adjustable Frequency AC Drive

Smart Start-Up with Basic Program Group Parameters

The PowerFlex 520-series drive is designed so that start-up is simple and efficient. The Basic Program group contains the
most commonly used parameters. See the PowerFlex 520-Series Adjustable Frequency AC Drive User Manual, publication
520-UM001
for detailed descriptions of the parameters listed here, as well as the full list of available parameters.
= Stop drive before changing this parameter.
= Parameter is specific to PowerFlex 525 drives only.
PF 525
No.
Parameter
P030
[Language]
Selects the language displayed.
Important: The setting takes effect after the drive is power cycled.
P031
[Motor NP Volts]
Sets the motor nameplate rated volts.
P032
[Motor NP Hertz]
Sets the motor nameplate rated frequency.
P033
[Motor OL Current]
Sets the motor nameplate overload current.
P034
[Motor NP FLA]
Sets the motor nameplate FLA.
P035
[Motor NP Poles]
Sets the number of poles in the motor.
P036
[Motor NP RPM]
Sets the rated nameplate rpm of motor.
P037
[Motor NP Power]
PF 525
Sets the motor nameplate power. Used in PM regulator.
P038
[Voltage Class]
Sets the voltage class of 600V drives. Only applicable to 600V drives.
P039
[Torque Perf Mode]
Selects the motor control mode.
(1) Setting is specific to PowerFlex 525 drives only.
P040
[Autotune]
Enables a static (not spinning) or dynamic (motor spinning) autotune.
P041
[Accel Time 1]
Sets the time for the drive to accel from 0 Hz to
[Maximum Freq].
P042
[Decel Time 1]
Sets the time for the drive to decel from [Maximum
Freq] to 0 Hz.
20
www.aotewell.com
Min/Max
1/15
10V (for 200V Drives), 20V (for 400V Drives),
25V (for 600V Drives) / Drive Rated Volts
15/500 Hz
0.0/(Drive Rated Amps x 2)
0.0/(Drive Rated Amps x 2)
2/40
0/24000 rpm
0.00/Drive Rated Power
2/3
0/3
0/2
0.00/600.00 s
0.00/600.00 s
Rockwell Automation Publication 520-QS001A-EN-E - March 2014
sales@aotewell.com
Industry Automation
Display/Options
Default
1 = English
1
2 = Français
3 = Español
4 = Italiano
5 = Deutsch
6 = Reserved
7 = Português
8 = Reserved
9 = Reserved
10 = Reserved
11 = Reserved
12 = Polish
13 = Reserved
14 = Turkish
15 = Czech
1V
Based on Drive Rating
0.1 A
60 Hz
0.1 A
Based on Drive Rating
0.1 A
Drive Rated Amps
1
4
1 rpm
1750 rpm
0.01 kW
Drive Rated Power
2 = "480V"
3
3 = "600V"
0 = "V/Hz"
1
1 = "SVC"
2 = "Economize"
(1)
3 = "Vector"
0 = "Ready/Idle"
0
1 = "Static Tune"
2 = "Rotate Tune"
0.01 s
10.00 s
0.01 s
10.00 s
+86-755-8660-6182

Advertisement

Table of Contents
loading

This manual is also suitable for:

Powerflex 525