P031 [Motor Np Volts]; P032 [Motor Np Hertz]; P033 [Motor Ol Current]; P034 [Minimum Freq] - Allen-Bradley PowerFlex400 User Manual

Adjustable frequency ac drive for fan & pump applications frn 4.xx
Table of Contents

Advertisement

Basic Program Group

P031 [Motor NP Volts]

Stop drive before changing this parameter.
Set to the motor nameplate rated volts.
Values
Default:
Min/Max:
Display:

P032 [Motor NP Hertz]

Stop drive before changing this parameter.
Set to the motor nameplate rated frequency.
Values
Default:
Min/Max:
Display:

P033 [Motor OL Current]

Set to the maximum allowable motor current.
The drive will fault on an F7
seconds.
Values
Default:
Min/Max:
Display:

P034 [Minimum Freq]

Sets the lowest frequency the drive will output continuously.
Values
Default:
Min/Max:
Display:
P035 [Maximum Freq]
Stop drive before changing this parameter.
Sets the highest frequency the drive will output.
Values
Default:
Min/Max:
Display:
Related Parameter(s): b004, A170, A171, A172,
Based on Drive Rating
20/Drive Rated Volts
1 VAC
Related Parameter(s): A170, A171, A172, A173, A181,
60 Hz
15/320 Hz
1 Hz
Related Parameter(s): P042, T055, T060, T065, A175, A179,
Motor Overload
if the value of this parameter is exceeded by 150% for 60
Drive Rated Amps
0.0/(Drive Rated Amps × 2)
0.1 Amps
Related Parameter(s): b001, b002, P035, T070, T074,
0.0 Hz
0.0/320.0 Hz
0.1 Hz
Related Parameter(s): b001, b002, P034, T071, T075,
60.0 Hz
0.0/320.0 Hz
0.1 Hz
Programming and Parameters
A171, A172, A173,
T083, T085, T086, A171, A172, A173,
3-7
A173
A182
A180, A181,
A183
d302
T082
d302