Section 4
IEC 60870-5-103 vendor specific implementation
4.1.7.4
Table 22:
I103SUPERV Non group settings (basic)
Name
FunctionType
4.1.7.5
4.1.8
4.1.8.1
30

Settings

Values (Range)
Unit
1 - 255
-

Supported information types

Supervision indications in monitor direction, I103SUPERV
Number of instances: 1
Function type is selected with parameter FunctionType.
Information number is defined for output signals.
Table 23:
I103SUPERV supported indications
Info. no.
Message
32
Measurand supervision I
33
Measurand supervision U
35
Phase sequence supervision
36
Trip circuit supervision
37
I>>back-up operation
38
VT fuse failure
39
Teleprotection disturbed
46
Group warning
47
Group alarm

Status for user defined signals for IEC 60870-5-103

I103USRDEF

Functionality

I103USRDEF is a function blocks with user defined input signals in monitor
direction. These function blocks include the FunctionType parameter for each
block in the private range, and the information number parameter for each input
signal.
I103USRDEF can be mapped to the INF that are not supported directly by specific
function blocks, for example: INF17, INF18, INF20 or INF35. After connecting
the appropriate signals to the I103USRDEF inputs, the user must also set the
InfNo_x values in the settings
Step
Default
1
1
Supported
Yes
Yes
No
No
Yes
Yes
No
Yes
Yes
1MRS757203 A
Description
Function type (1-255)
Type
GI
1
Y
1
Y
1
Y
1
Y
1
Y
1
Y
1
Y
1
Y
1
Y
Communication Protocol Manual
COT
1,7,9
1,7,9
1,7,9
1,7,9
1,7,9
1,7,9
1,7,9
1,7,9
1,7,9
630 series