Putting Into Operation, Operating Mode C (D Series Only) - IVT Greenline D14 Manual To Installation, Commissioning And Maintenance

Table of Contents

Advertisement

Commissioning operating mode C
Connect the mains voltage to the heat pump and press the ON/OFF button on the control panel.
Rego 600 measures the phase sequence so that the compressor does not run in the wrong direction,
so if you receive an phase sequence alarm the main supply is cut to the heat pump and two of the
phases are shifted.
Press "Menu" for 10 seconds to come into the Installer / service menu. I/S should be visible at the
top right hand corner.
Go into display 5.1 and choose operating mode C.
Heat setting Heat incr/decr can temporarily be set on max. To avoid having to wait for the heat pump
restart menu you can go to display 5.6 and quick start the heat pump. If the pump does not start,
press "Info" to see what the reason is. When the heat pump starts, check the sight glass in the heat
pump. When starting there may be bubbles in the sight glass for a minute or so, after which they
should disappear. If there are bubbles present all the time the heat pump is running, this is a fault
symptom. They are probably due to air in the collector hose or insufficient heat transfer fluid.
Check that the operational condition of the heat pump corresponds to the information supplied in the
Info menu.
There are always some settings you have to check or adjust and some you might need to change if
they require another setting than the factory setting.
Displays you must always check
Commiss./Service
Select operation
mode
A B C
Return
Select
Commiss./Service
Select conn capacity
electrical cass. 5.2
Return
Select
Commiss./Service
Connected extra
sensor in op.
Return
Select
Displays you might need to adjust or check settings
Temperature settings
Mixing valve curve
neutral zone
Return
Select
Temperature settings
Mixing valve curve
max at GT4
Return
Select
Choose operating mode C so that Rego 600 memorises the
operation with a fixed temperature.
5.1
Setting maximum output to be used by the electric heater.
You can choose 1/3, 2/3 or 3/3.
must be fused protected for the set ouput. Factory setting is
2/3. See description below in technical specifications.
If you have connected any of the external sensors
T4 (GT4) or T5 (GT5) you must Ackn them so that Rego
5.13
600 memorises them.
If you use a mixing valve you can set the neutral zone for
Only with
the mixing valve. In the neutral zone nobody can open or
T4 (GT4)
1.8
shut the signal.
Setting the maximum temperature in the mixing valve circuit.
Only with
T4 (GT4)
Factory setting is 60ºC.
1.9
59
(D series only)
The heat pump

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents