IVT Greenline D14 Manual To Installation, Commissioning And Maintenance page 24

Table of Contents

Advertisement

ALARM
Low pressure switch
020301 15:10:18
Info
Probable causes and actions:
• Air in the heating system.
Action: Check the expansion vessel and fill if required. If air is heard continuously in the system,
contact the installer.
• Heat transfer pump has stopped or is set at too low a speed.
Action: Check the pump has not stopped or is set at the wrong speed.
• Particle filter on the cold side is clogged.
Action: Check the particle filter and clean if necessary.
• Not enough refrigerant in the circuit.
Action:Check that bubbles do not appear continuously in the sight glass. Contact the installer.
• Not enough antifreeze in the heat transfer circuit creating ice in the heat exchanger.
Action: Contact the installer.
• Expansion valve faulty (alarms occur at long intervals, about every three or four weeks).
Action: Contact the installer.
ALARM
High press. switch
020301 15:10:18
Info
Probable causes and actions:
• Air in the heating system.
Action: Check the system and vent the radiators if necessary.
• Not enough flow over the heat pump.
Action:Check that the circulation pump has not stopped and that a valve in the system is not closed.
• Particle filter on the hot side is clogged.
Action: Check the particle filter and clean if necessary.
• Heat transfer fluid circuit over-filled.
Action: Contact the installer.
• Drying filter clogged.
Action: Contact the installer.
LOW PRESSURE SWITCH ALARM
(LP)
To reset the alarm:
Press "Ackn."
Ackn.
HIGH PRESSURE SWITCH ALARM
(HP)
To reset the alarm:
Press "Ackn."
Ackn.