GE MiCOM P40 Agile P14D Manual page 6

Advertisement

Version History
Software
Hardware
Original Date of
Version
Suffix
Issue
Major Minor
B
A
Apr-15
54
C
A
April-2017
55
A
A
November-15
6
Relay type: Agile P14N, P14D and P94V
 Agile Relay failure: Error/Lockout 7104:2000/reboot
 The LCD display year is 2080 but in the disturbance and event records it is 1980.
 Using S1 Agile changing values to the Voltage Transformer does not change the corresponding vaues in Residual
O/V NVD column
 Line length mismatch between value sent from S1 Agile and the value received in the relay
 DNP3oE Setting Files - GoEna is visible
 Values under High impedance menu do not show values in primary when relay is set to primary in S1.
IEC 61850 - Connection / Disconnection issues
DNP3oE Versions - Courier Tunnelling does not work
DNPOE after operated some DI and AI events at the same time, the relay Ethernet board seems locked and after a
while the relay reboot.
Permanent Ethernet communication loss in P40 Agile relays
TCP disrupts after around 206 days of continuous use
P14DZ HiZ Function asserting incorrectly (CHA HiF)
Incorrect Burst Count - HiF Detection
FA Steady Fault - Incorrect Assertion
HIF CHA Hysteresis is not correctly set
HIF Burst Threshold is not reset after the adaptive threshold is disabled
Maintenance Record Generated Everytime Gateway is configured in DNP configuration
CS1 and CS2 does not work independently whey CB Comp enabled for CS2
· To retrofit legacy products KAVR100, KAVS and KVTR
· Pin to pin retrofit solution for KMPC130
· Compliance to CEI 0-16 requirements in P14D/P94V
· New communication protocol options - 1)IEC61850 over Ethernet + Modbus via RS485, 2)IEC61850 over
Ethernet + DNP3.0 via RS485
· Settable k factor in Thermal overload
· Fault locator setting improvements
· Earth Fault (EF1) setting 10mA minimum threshold
· DNP3.0 Unsolicited message reporting
· PSL timer setting
· New extra shorting link ordering option – for capacitor cone NVD application & alarm on IED removal
· Compliance to Russian Rosseti requirements
· NCIT column visibility incorrect.
· Write 'AAAA' into cell 0x0002 failed with a reply code 05(CS103_GRC_SETTING_OUT_OF_RANGE)
· Generated MICS document for IEC 61850 protocol contains 'IEC61850' instead of 'IEC 61850".
· Can not extract Disturbance records from a P545 DNP3 OE using DNP3 commands
· P145 reboots periodically when IEC 61850 comms active and SNTP active
· Status report over IEC61850 not in line with DDB signals
Description of Changes
P40 Agile P14D, P14N, P94V
Technical Documentation
P14D-TM-EN-4.1
P14N-TM-EN-4.1
P94V-TM-EN-4.1
P14D-TM-EN-5
P14N-TM-EN-5
P94V-TM-EN-5
P40Agile-VH-EN-9

Advertisement

loading

This manual is also suitable for:

Micom p40 agile p14nMicom p40 agile p94v