GE MiCOM P40 Agile P14D Manual page 9

Advertisement

P40 Agile P14D, P14N, P94V
Software
Hardware
Original Date of
Version
Suffix
Issue
Major Minor
55
B
A
October-16
56
A
A
February-16
57
A
A
May-15
57
B
A
April-2017
P40Agile-VH-EN-9
Relay type: Agile P14N, P14D and P94V
The values of DDBs (1717~1720) read via IEC61850 can not be updated after downloading the new PSL
The fault record can't be extracted via CS103 protocol if the previous fault record terminated by "Reset CU".
DNP Over Ethernet Application Crash after many days of Polling
Permanent ethernet communication loss in P40 Agile relays in MICHELIN Site (ACT 160622 – 45574)
After enabling the BRCB, the first integrity report comes out around 10s when the integrity time is set to be 3s
under certain pre-steps
P14DZ HiZ Function asserting incorrectly (CHA HiF)
Incorrect Burst Count - HiF Detection
FA Steady Fault - Incorrect Assertion
HIF CHA Hysteresis is not correctly set
HIF Burst Threshold is not reset after the adaptive threshold is disabled
· PRP / HSR / FailOver redundancy (new hardware boards) Configurable Fail-over in DNP3
· DDB 781/782 doesn't show the real status when the alarm "Port A Link Fail" or "Port B Link Fail" show in HMI
· The status of DDB 783 is "OFF" issue
· RSTP redundancy (new hardware boards)
· PCCN/Electre features
· CEI 0-16 2nd round
· DNP3 memory leak correction (AGPL-49)
· The values of DDBs (1717~1720) read via IEC61850 can not be updated after downloading the new PSL
· The fault record can't be extracted via CS103 protocol if the previous fault record terminated by "Reset CU".
· DNP Over Ethernet Application Crash after many days of Polling
· DDB #146 "Prot'n Disabled" events are read as "test mode" via CS103 protocol.
· The new under voltage Average voltage protections doesn't use POLEDEAD similar to the standard under voltage
· Ext AR SEF Trip could not block AR when [493F] SEF Ext Prot is set to "Block AR".
· The VTS Fast Block can not block the AVG undervoltage;AVG overvoltage;AVG ZERO SEQ O/V;AVG POS SEQ
O/V and AVG NEG SEQ O/V
· DDB #167 UV Block should not be visible on P14DA.
· After enabling the BRCB, the first integrity report comes out around 10s when the integrity time is set to be 3s
under certain pre-steps
· IEC 61850 client sets unsupported TrgOps must have response+ (Tissue 780)
· P14DZ HiZ Function asserting incorrectly (CHA HiF)
· Incorrect Burst Count - HiF Detection
· FA Steady Fault - Incorrect Assertion
· HIF CHA Hysteresis is not correctly set
· HIF Burst Threshold is not reset after the adaptive threshold is disabled
Permanent ethernet communication loss in P40 Agile relays in MICHELIN Site
Maintenance Record Generated Everytime Gateway is configured in DNP configuration
Description of Changes
Version History
Technical Documentation
P14D-TM-EN-6.1
P14N-TM-EN-6.1
P94V-TM-EN-6.1
P14D-TM-EN-7
P14N-TM-EN-7
P94V-TM-EN-7
9