GE MiCOM P40 Agile P14D Manual page 7

Advertisement

P40 Agile P14D, P14N, P94V
Software
Hardware
Original Date of
Version
Suffix
Issue
Major Minor
P40Agile-VH-EN-9
Relay type: Agile P14N, P14D and P94V
· actVal Data Attribute now finalised as INT32 requirement in SCL (Edition 1 Only)
· Values under High impedance menu do not show values in primary when relay is set to primary in S1.
· Pending Reports when BufTm>0? Ed1
· Agile latch reset when setting group is changed
· Connection / Disconnection issues
· Class 0 should be configurable to select either Counter or corresponding Frozen Counter
· DNP3oE Versions - Courier Tunnelling doesnot work
· For DNPOE build, the frozen counter always keeps the same value with the static counter without accepting a
Freeze command.
· The behaviour of frozen counter is different between DNP3 and DNPOE before the freeze command is sent
· DNPOE after operated some DI and AI events at the same time ,the relay Ethernet board seems locked and after
a while the relay reboot.
· IEC 61850 Interoperability problem when a client writes to any/all unsupported Trigger Options
· Problems with ICD files for P140 50A
· 8.333Hz is displayed in the first generated Fault Record after relay reboot.
· P145 Underfrequency issue in Russia
· SecRmsMMXU1 showing values in primary, not secondary
· IEC 61850: incorrect Courier cell mapping to TotWh and TotVArh in MMTR LNs
· CB Fail trip may fail to operate under faults with DC transient offsets
· "FUNCTION KEYS" column is visible for 20TE devices in P14 Agile data model.
· Default GOOSE "Min Cycle Time" is wrong.
· Visibility of setting "I>1 TMS" and "I>1 Time Dial" is wrong in Group 2
· EPATR-B curve
· High Impedance Fault issue
· DNP3OE Versions - Command management during IED disconnection / connection
· Freq Avg Cycles & df/dt Avg Cycles should use power cycle instead of PCON calls cycles
· The unit of Records/RFLO1/CF/FltDiskm is incorrect
· Very sharp pick current level lead relay tripping on IREF
· The error message" Runtime Error C991:3011" appear on P14N relay when glance over the cells in overcurrent
column from HMI
· Column [4E00] PSL TIMERS is invisible from relay
· Default Setting of Relay is in-consistent to Look & Feel
· P94VR Look & Feel consistency check issues via courier interface
· "Ethernet failover" option displays in IED Configurator
· New settings Moving average cells ([42 41] -> [42 2D]) are not working in Modbus.
· When download the software to the P14DZ relay and power cycle,the error message - "Runtime Error
2e0b:0101" appear and relay reboot
· The sequence number should not increase when relay send retry unsolicited message
Description of Changes
Version History
Technical Documentation
7