9.1 SETTING EXAMPLE
Since this element will coordinate with system protections a timed reset is chosen. The element must be blocked for a VT
fuse failure. The neutral source will be chosen. Make the following changes in EnerVista UR Setup or through the
GROUPED ELEMENTS
This protection should be set to coordinate with the manufacturers excitation capability curves. For example system, the
combined generator/GSU limit curve is shown below:
Program the volts per hertz 1 element with an inverse characteristic (curve A), a pickup of 1.05, and a TDM of 40. Program
9
the volts per hertz 2 element with a definite time characteristic, a pickup of 1.23, and a time delay of 2 seconds. Both ele-
ments will issue a trip. The volts per hertz 1 pickup will be used to generate an alarm. Either source may be assigned in this
example. Make the following changes in EnerVista UR Setup or through the
9-10
SETTING GROUP 1
PHASE CURRENT
Combined generator/GSU
limit curve
Figure 9–5: GENERATOR/GSU LIMIT CURVE
G30 Generator Protection System
menu:
PHASE TOC1
Volts per hertz (p.u.)
Volts per
hertz 1
SETTINGS
9 APPLICATION OF SETTINGS
SETTINGS
9.1.9 OVEREXCITATION
Volts per
hertz 2
830734A1.CDR
GROUPED ELEMENTS
GE Multilin
SET-