GE G30 Instruction Manual page 516

Ur series generator protection system
Hide thumbs Also See for G30:
Table of Contents

Advertisement

B.4 MEMORY MAPPING
Table B–10: MODBUS MEMORY MAP (Sheet 28 of 60)
ADDR
REGISTER NAME
Setting Groups (Read/Write Setting)
5F70
Setting Group for Modbus Comms (0 means group 1)
5F71
Setting Groups Block
5F73
FlexLogic Operands to Activate Groups 2 through 6 (5
items)
B
5F7D
Setting Group Function
5F7E
Setting Group Events
Setting Groups (Read Only)
5F7F
Current Setting Group
Setting Group Names (Read/Write Setting)
5F8C
Setting Group 1 Name
5F94
Setting Group 2 Name
5F9C
Setting Group 3 Name
5FA4
Setting Group 4 Name
5FAC
Setting Group 5 Name
5FB4
Setting Group 6 Name
Transformer Percent Differential (Read/Write Grouped Setting)
61C0
Percent Differential Function
61C1
Percent Differential Pickup
61C2
Percent Differential Slope 1
61C3
Percent Differential Break 1
61C4
Percent Differential Break 2
61C5
Percent Differential Slope 2
61C6
Inrush Inhibit Function
61C7
Inrush Inhibit Level
61C8
Overexcitation Inhibit Function
61C9
Overexcitation Inhibit Level
61CA
Percent Differential Block
61CC
Percent Differential Target
61CD
Percent Differential Events
61CE
Transformer Inrush Inhibit Mode
Negative Sequence Overvoltage (Read/Write Grouped Setting) (3 modules)
6440
Negative Sequence Overvoltage Function
6441
Negative Sequence Overvoltage Source
6442
Negative Sequence Overvoltage Pickup
6443
Negative Sequence Overvoltage Pickup Delay
6444
Negative Sequence Overvoltage Reset Delay
6445
Negative Sequence Overvoltage Block
6447
Negative Sequence Overvoltage Target
6448
Negative Sequence Overvoltage Events
6449
...Repeated for module number 2
6452
...Repeated for module number 3
Overfrequency (Read/Write Setting) (4 modules)
6470
Overfrequency 1 Function
6471
Overfrequency 1 Block
6473
Overfrequency 1 Source
6474
Overfrequency 1 Pickup
6475
Overfrequency 1 Pickup Delay
6476
Overfrequency 1 Reset Delay
6477
Overfrequency 1 Target
6478
Overfrequency 1 Events
6479
Reserved (4 items)
647D
...Repeated for Overfrequency 2
648A
...Repeated for Overfrequency 3
B-36
RANGE
0 to 5
0 to 4294967295
0 to 4294967295
0 to 1
0 to 1
0 to 5
---
---
---
---
---
---
0 to 1
0.05 to 1
15 to 100
1 to 2
2 to 30
50 to 100
0 to 2
1 to 40
0 to 1
1 to 40
0 to 4294967295
0 to 2
0 to 1
0 to 2
0 to 1
0 to 5
0 to 1.25
0 to 600
0 to 600
0 to 4294967295
0 to 2
0 to 1
0 to 1
0 to 4294967295
0 to 5
20 to 65
0 to 65.535
0 to 65.535
0 to 2
0 to 1
0 to 1
G30 Generator Protection System
APPENDIX B
UNITS
STEP
FORMAT
---
1
F001
---
1
F300
---
1
F300
---
1
F102
---
1
F102
---
1
F001
---
---
F203
---
---
F203
---
---
F203
---
---
F203
---
---
F203
---
---
F203
---
1
F102
pu
0.001
F001
%
1
F001
pu
0.001
F001
pu
0.001
F001
%
1
F001
---
1
F168
1 (Adapt. 2nd)
%fo
0.1
F001
---
1
F169
%fo
0.1
F001
---
1
F300
---
1
F109
---
1
F102
---
1
F189
---
1
F102
---
1
F167
pu
0.001
F001
s
0.01
F001
s
0.01
F001
---
1
F300
---
1
F109
---
1
F102
---
1
F102
---
1
F300
---
1
F167
Hz
0.01
F001
s
0.001
F001
s
0.001
F001
---
1
F109
---
1
F102
---
1
F001
DEFAULT
0
0
0
0 (Disabled)
0 (Disabled)
0
(none)
(none)
(none)
(none)
(none)
(none)
0 (Disabled)
100
25
2000
8000
100
200
0 (Disabled)
100
0
0 (Self-reset)
0 (Disabled)
0 (Per phase)
0 (Disabled)
0 (SRC 1)
300
50
50
0
0 (Self-reset)
0 (Disabled)
0 (Disabled)
0
0 (SRC 1)
6050
500
500
0 (Self-reset)
0 (Disabled)
0
GE Multilin

Advertisement

Table of Contents
loading

Table of Contents