Rated input power
BTUs per hour
Power supply output
Rated steady-state power
Rated peak power
CAUTION:
This equipment is designed to permit the connection of the earthed conductor of
the DC supply circuit to the earthing conductor at the equipment. See installation instructions.
CAUTION:
This equipment is designed to permit the connection of the earthed conductor of
the DC supply circuit to the earthing conductor at the equipment.
If this connection is made, all of the following must be met:
CAUTION:
To reduce the risk of electric shock or energy hazards:
1380 W at -36V DC input
1365 W at -72V DC input
1350 W at -48V DC, nominal
input
4713 at -36V DC input
4662 at -72V DC input
4610 at -48V DC, nominal input
1200 W
1200 W
This equipment should be connected directly to the DC supply system earthing
electrode conductor or to a bonding jumper from an earthing terminal bar or
bus to which the DC supply system earthing electrode conductor is connected.
This equipment should be located in the same immediate area (such as
adjacent cabinets) as any other equipment that has a connection between the
earthed conductor of the same DC supply circuit and the earthing conductor,
and also the the point of earthing of the DC system. The DC system should be
earthed elsewhere.
The DC supply source is to be located within the same premises as the
equipment.
Switching or disconnecting devices should not be in the earthed circuit
conductor between the DC source and the point of connection of the earthing
electrode conductor.
This equipment must be installed by trained service personnel, as defined by
the NEC and IEC 60950-1, Second Edition, the standard for Safety of
Information Technology Equipment.
Connect the equipment to a reliably grounded safety extra low voltage (SELV)
source. An SELV source is a secondary circuit that is designed so normal and
single fault conditions do not cause the voltages to exceed a safe level (60 V
direct current).
The branch circuit overcurrent protection must be rated 20A.
Specifications 81