Example: Network Read and Network Write Instructions
S7-200 Instruction Set
Network 1
//On the first scan, enable the PPI master mode
/and clear all receive and transmit buffers.
LD
SM0.1
MOVB
2, SMB30
FILL
+0, VW200, 68
Network 2
//When the NETR Done bit (V200.7) is set
//and 100 cases have been packed:
//1. Load the station address of case packer #1.
//2. Load a pointer to the data in the remote station.
//3. Load the length of data to be transmitted.
//4. Load the data to transmit.
//5. Reset the number of cases packed
//
by case packer #1
LD
V200.7
AW=
VW208, +100
MOVB
2, VB301
MOVD
&VB101, VD302
MOVB
2, VB306
MOVW
+0, VW307
NETW
VB300, 0
Network 3
//When the NETR Done bit is set, save the control
//data from case packer #1.
LD
V200.7
MOVB
VB207, VB400