S7-200 Programmable Controller System Manual
Input Data Word Format for EM 231 and EM 235
Figure A-11 shows where the 12-bit data value is placed within the analog input word of the CPU.
Figure A-11
Tip
The 12 bits of the analog-to-digital converter (ADC) readings are left-justified in the data word format.
The MSB is the sign bit: zero indicates a positive data word value.
In the unipolar format, the three trailing zeros cause the data word to change by a count of eight for
each one-count change in the ADC value.
In the bipolar format, the four trailing zeros cause the data word to change by a count of sixteen for each
one count change in the ADC value.
Input Block Diagram for EM 231 and EM 235