Danfoss ECL Comfort 210 Operating Manual page 22

Hide thumbs Also See for ECL Comfort 210:
Table of Contents

Advertisement

Operating Guide ECL Comfort 210/296/310, application A275/A375
A275.2, example b
Boiler ON / OFF control for a heating and a DHW circuit. DHW priority.
* = pressure relief valve
At DHW heating P3 (changeover valve) is activated and the desired boiler temperature lies a number of degrees above the desired DHW
temperature.
P1 is continuously switched ON.
Special settings for type A275.2, example b:
Navigation:
DHW circuit (circuit 2)
DHW heating is managed by changeover valve P3 / M1:
MENU \ Settings \ Application: 'Ch.-o. valve / P'
The desired DHW heating temperature must influence the desired boiler temperature:
MENU \ Settings \ Application: 'Tank, sec./prim.'
22 | © Danfoss | 2017.09
ID no.:
Recommended setting:
12051
OFF
12053
OFF
VI.GU.L2.02