Danfoss ECL Comfort 210 Operating Manual page 125

Hide thumbs Also See for ECL Comfort 210:
Table of Contents

Advertisement

Operating Guide ECL Comfort 210/296/310, application A275/A375
MENU > Settings > Optimization
Total stop
Decide whether you want a total stop during the saving temperature period.
See Appendix "Parameter ID overview"
OFF:
No total stop. The desired flow temperature is reduced
according to:
• desired room temperature in saving mode
• auto saving
ON:
The desired flow temperature is lowered to the set value
in 'Frost pr. ' The circulation pump is stopped but frost
protection is still active, see 'P frost T' .
MENU > Settings > Optimization
Pre-stop (optimized stop time)
Disable the optimized stop time.
See Appendix "Parameter ID overview"
OFF:
The optimized stop time is disabled.
ON:
The optimized stop time is enabled.
VI.GU.L2.02
Total stop = OFF
1x021
Total stop = ON
= Time
X
= Desired flow temperature
Y
= Comfort temperature
= Saving temperature
= Frost protection
The min. flow temperature limitation ('Temp. min.') is overruled when
'Total stop' is ON.
Example: Optimization of Comfort from 07:00 - 22:00
1x026
=
X
Time
=
# 1#
Schedule
=
# 2 #
Prestop = OFF
=
# 3 #
Prestop = ON
=
# 4 #
Optimized start
=
# 5 #
Optimized stop
© Danfoss | 2017.09 | 125