Operating Guide ECL Comfort 210/296/310, application A275/A375
A275.2, example a
Boiler ON / OFF control for a heating and a DHW circuit. Optional DHW priority.
* = pressure relief valve
At DHW heating P3 is switched ON and the desired boiler temperature lies a number of degrees above the desired DHW temperature.
P1 is switched OFF.
Special settings for type A275.2, example a:
Navigation:
DHW circuit (circuit 2)
DHW heating is managed by pump P3:
MENU \ Settings \ Application: 'Ch.-o. valve / P'
The desired DHW heating temperature must influence the desired boiler temperature:
MENU \ Settings \ Application: 'Tank, sec./prim.'
Please note:
If 'Ch.-o. valve / P' in 12051 is set to OFF, P3 will be switched on at DHW heating. The desired boiler temperature will still lie a
number of degrees above the desired DHW temperature and P1 will remain switched ON.
VI.GU.L2.02
ID no.:
Recommended setting:
12051
ON
12053
OFF