Danfoss ECL Comfort 210 Operating Manual page 120

Hide thumbs Also See for ECL Comfort 210:
Table of Contents

Advertisement

Operating Guide ECL Comfort 210/296/310, application A275/A375
MENU > Settings > Return limit
Priority (priority for return temp. limitation)
Choose whether the return temperature limitation should overrule the set
min. flow temperature 'Temp. min.' .
See Appendix "Parameter ID overview"
OFF:
The min. flow temperature limit is not overruled.
ON:
The min. flow temperature limit is overruled.
120 | © Danfoss | 2017.09
1x085
If you have a DHW application:
Please also see 'Parallel operation' (ID 11043).
If you have a DHW application:
When dependent parallel operation is in function:
Desired flow temperature for the heating circuit will be minimum
limited, when "Priority for return temperature" (ID 1x085) is set
to OFF.
Desired flow temperature for the heating circuit will not be
minimum limited, when "Priority for return temperature"
(ID 1x085) is set to ON.
VI.GU.L2.02