Danfoss ECL Comfort 210 Operating Manual page 176

Hide thumbs Also See for ECL Comfort 210:
Table of Contents

Advertisement

Operating Guide ECL Comfort 210/296/310, application A275/A375
ECA MENU > ECA system > ECA communication
Connection addr. (Connection address)
Setting range
1 ... 9 / 15
Setting of the address to which ECL controller the
communication must run.
1 .. 9:
Slave controllers.
15:
Master controller.
ECA MENU > ECA system > ECA override
Override addr. (Override address)
Setting range
OFF / 1 ... 9 / 15
The feature 'Override' (to extended comfort or
saving period or holiday) must be addressed to the
ECL controller in question.
OFF:
Override not possible.
1 .. 9:
Address of slave controller for override.
15:
Address of master controller for override.
176 | © Danfoss | 2017.09
Factory setting
15
Factory setting
OFF
An ECA 30 / 31 can in an ECL 485 bus system (master – slave) be set to
communicate, one by one, with all addressed ECL controllers.
Example:
Connection addr. = 15: The ECA 30 / 31 communicates with the
ECL master controller.
Connection addr. = 2:
The ECA 30 / 31 communicates with the
ECL controller with address 2.
There must be a master controller present in order to broadcast time
and date information.
An ECL Comfort controller 210 / 310, type B (without display and dial)
cannot be assigned to the address 0 (zero).
Extended saving mode:
Extended comfort mode:
Override functions:
Holiday away from home:
Holiday at home:
Override by means of settings in ECA 30 / 31 are cancelled if the ECL
Comfort controller goes into holiday mode or is changed to another
mode than scheduled mode.
The circuit in question for override in the ECL controller must be in
scheduled mode.
See also the parameter 'Override circuit' .
VI.GU.L2.02