GE UR Series F60 Instruction Manual page 423

Feeder protection system
Hide thumbs Also See for UR Series F60:
Table of Contents

Advertisement

APPENDIX B
Table B–9: MODBUS MEMORY MAP (Sheet 35 of 51)
ADDR
REGISTER NAME
A90A
Frequency Rate of Change 1 Trend
A90B
Frequency Rate of Change 1 Pickup
A90C
Frequency Rate of Change 1 OV Supervision
A90D
Frequency Rate of Change 1 Reserved (3 items)
A910
...Repeated for Frequency Rate of Change 2
A920
...Repeated for Frequency Rate of Change 3
A930
...Repeated for Frequency Rate of Change 4
IEC 61850 received analog settings (read/write)
AA00
IEC 61850 GOOSE analog 1 default value
AA02
IEC 61850 GOOSE analog input 1 mode
AA03
IEC 61850 GOOSE analog input 1 units
AA05
IEC 61850 GOOSE analog input 1 per-unit base
AA07
...Repeated for IEC 61850 GOOSE analog input 2
AA0E
...Repeated for IEC 61850 GOOSE analog input 3
AA15
...Repeated for IEC 61850 GOOSE analog input 4
AA1C
...Repeated for IEC 61850 GOOSE analog input 5
AA23
...Repeated for IEC 61850 GOOSE analog input 6
AA2A
...Repeated for IEC 61850 GOOSE analog input 7
AA31
...Repeated for IEC 61850 GOOSE analog input 8
AA38
...Repeated for IEC 61850 GOOSE analog input 9
AA3F
...Repeated for IEC 61850 GOOSE analog input 10
AA46
...Repeated for IEC 61850 GOOSE analog input 11
AA4D
...Repeated for IEC 61850 GOOSE analog input 12
AA54
...Repeated for IEC 61850 GOOSE analog input 13
AA5B
...Repeated for IEC 61850 GOOSE analog input 14
AA62
...Repeated for IEC 61850 GOOSE analog input 15
AA69
...Repeated for IEC 61850 GOOSE analog input 16
IEC 61850 GOOSE/GSSE Configuration (Read/Write Setting)
AA80
Default GOOSE/GSSE Update Time
AA81
IEC 61850 GSSE Function (GsEna)
AA82
IEC 61850 GSSE ID
AAA3
IEC 61850 GOOSE Function (GoEna)
AAA4
IEC 61850 GSSE Destination MAC Address
AAA7
IEC 61850 Standard GOOSE ID
AAC8
IEC 61850 Standard GOOSE Destination MAC Address
AACB
IEC 61850 GOOSE VLAN Transmit Priority
AACC
IEC 61850 GOOSE VLAN ID
AACD
IEC 61850 GOOSE ETYPE APPID
AACE
Reserved (2 items)
IEC 61850 Server Configuration (Read/Write Settings/Commands)
AAD0
TCP Port Number for the IEC 61850 / MMS Protocol
AAD1
IEC 61850 Logical Device Name
AAE1
IEC 61850 Logical Device Instance
AAF1
IEC 61850 LPHD Location
AB19
Include non-IEC 61850 Data
AB1A
IEC 61850 Server Data Scanning Function
AB1B
Command to Clear XCBR1 OpCnt (operation counter)
AB1C
Command to Clear XCBR2 OpCnt (operation counter)
AB1D
Reserved (15 items)
IEC 61850 GGIO4 general analog configuration settings (read/write)
AF00
Number of analog points in GGIO4
IEC 61850 GGIO4 analog input points configuration settings (read/write)
AF10
IEC 61850 GGIO4 analog input 1 value
AF11
IEC 61850 GGIO4 analog input 1 deadband
GE Multilin
RANGE
0 to 2
0.1 to 15
0.1 to 3
0 to 1
–1000000 to 1000000
0 to 1
---
0 to 999999999.999
1 to 60
0 to 1
---
0 to 1
---
---
---
0 to 7
0 to 4095
0 to 16383
0 to 1
1 to 65535
---
---
---
0 to 1
0 to 1
0 to 1
0 to 1
4 to 32
---
0.001 to 100
F60 Feeder Protection System
B.4 MEMORY MAPPING
UNITS
STEP
FORMAT
---
1
F224
Hz/s
0.01
F001
pu
0.001
F001
---
1
F001
---
0.001
F060
---
1
F491
0 (Default Value)
---
---
F207
---
0.001
F060
s
1
F001
---
1
F102
---
---
F209
---
1
F102
---
---
F072
---
---
F209
---
---
F072
---
1
F001
---
1
F001
---
1
F001
---
1
F001
---
1
F001
---
---
F213
---
---
F213
---
---
F204
---
1
F102
---
1
F102
---
1
F126
---
1
F126
---
4
F001
---
---
F600
%
0.001
F003
DEFAULT
0 (Increasing)
50
700
0
B
1000
(none)
1
60
1 (Enabled)
"GSSEOut"
0 (Disabled)
0
"GOOSEOut"
0
4
0
0
0
102
"IECName"
"LDInst"
"Location"
0 (Disabled)
0 (Disabled)
0 (No)
0 (No)
4
0
100000
B-43

Advertisement

Table of Contents
loading

Table of Contents