GE UR Series F60 Instruction Manual page 141

Feeder protection system
Hide thumbs Also See for UR Series F60:
Table of Contents

Advertisement

5 SETTINGS
j) IEC 60870-5-104 PROTOCOL
PATH: SETTINGS
PRODUCT SETUP
IEC 60870-5-104
PROTOCOL
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
The F60 supports the IEC 60870-5-104 protocol. The F60 can be used as an IEC 60870-5-104 slave device connected to a
maximum of two masters (usually either an RTU or a SCADA master station). Since the F60 maintains two sets of IEC
60870-5-104 data change buffers, no more than two masters should actively communicate with the F60 at one time.
The
IEC ------- DEFAULT THRESHOLD
M_ME_NC_1 analog data. These settings group the F60 analog data into types: current, voltage, power, energy, and other.
Each setting represents the default threshold value for all M_ME_NC_1 analog points of that type. For example, to trigger
spontaneous responses from the F60 when any current values change by 15 A, the
ting should be set to 15. Note that these settings are the default values of the deadbands. P_ME_NC_1 (parameter of mea-
sured value, short floating point value) points can be used to change threshold values, from the default, for each individual
M_ME_NC_1 analog point. Whenever power is removed and re-applied to the F60, the default thresholds will be in effect.
The IEC 60870-5-104 and DNP protocols cannot be simultaneously. When the
ting is set to "Enabled", the DNP protocol will not be operational. When this setting is changed it will not
become active until power to the relay has been cycled (off-to-on).
NOTE
k) SNTP PROTOCOL
PATH: SETTINGS
PRODUCT SETUP
SNTP PROTOCOL
MESSAGE
MESSAGE
The F60 supports the Simple Network Time Protocol specified in RFC-2030. With SNTP, the F60 can obtain clock time over
an Ethernet network. The F60 acts as an SNTP client to receive time values from an SNTP/NTP server, usually a dedicated
product using a GPS receiver to provide an accurate time. Both unicast and broadcast SNTP are supported.
GE Multilin
COMMUNICATIONS
IEC 60870-5-104 PROTOCOL
IEC 60870-5-104
FUNCTION: Disabled
IEC TCP PORT
NUMBER: 2404
IEC NETWORK
CLIENT ADDRESSES
IEC COMMON ADDRESS
OF ASDU:
0
IEC CYCLIC DATA
PERIOD:
60 s
IEC CURRENT DEFAULT
THRESHOLD: 30000
IEC VOLTAGE DEFAULT
THRESHOLD: 30000
IEC POWER DEFAULT
THRESHOLD: 30000
IEC ENERGY DEFAULT
THRESHOLD: 30000
IEC OTHER DEFAULT
THRESHOLD: 30000
settings are used to determine when to trigger spontaneous responses containing
COMMUNICATIONS
SNTP PROTOCOL
SNTP FUNCTION:
Disabled
SNTP SERVER IP ADDR:
0.0.0.0
SNTP UDP PORT
NUMBER: 123
F60 Feeder Protection System
5.2 PRODUCT SETUP
Range: Enabled, Disabled
Range: 1 to 65535 in steps of 1
Range: 0 to 65535 in steps of 1
Range: 1 to 65535 s in steps of 1
Range: 0 to 65535 in steps of 1
Range: 0 to 65535 in steps of 1
Range: 0 to 65535 in steps of 1
Range: 0 to 65535 in steps of 1
Range: 0 to 65535 in steps of 1
IEC CURRENT DEFAULT THRESHOLD
IEC 60870-5-104 FUNCTION
Range: Enabled, Disabled
Range: Standard IP address format
Range: 0 to 65535 in steps of 1
5
set-
set-
5-29