Monitoring Elements - GE UR Series F60 Instruction Manual

Feeder protection system
Hide thumbs Also See for UR Series F60:
Table of Contents

Advertisement

5.6 CONTROL ELEMENTS
a) MAIN MENU
PATH: SETTINGS
CONTROL ELEMENTS
MONITORING
ELEMENTS
b) HIGH IMPEDANCE FAULT DETECTION
5
PATH: SETTINGS
CONTROL ELEMENTS
HI-Z
5-174

MONITORING ELEMENTS

HI-Z
BREAKER 1
MESSAGE
ARCING CURRENT
BREAKER 2
MESSAGE
ARCING CURRENT
BREAKER
MESSAGE
FLASHOVER 1
BREAKER
MESSAGE
FLASHOVER 2
VT FUSE FAILURE 1
MESSAGE
VT FUSE FAILURE 2
MESSAGE
MONITORING ELEMENTS
HI-Z FUNCTION:
Disabled
HI-Z SOURCE:
MESSAGE
SRC 1
HI-Z ARCING
MESSAGE
SENSITIVITY:
HI-Z ARCING DET SOE
MESSAGE
RESET TIME: 0.0 s
HI-Z PHASE EVENT
MESSAGE
COUNT:
30
HI-Z GROUND EVENT
MESSAGE
COUNT:
30
HI-Z EVENT COUNT
MESSAGE
TIME:
15 min
HI-Z OC PROTECTION
MESSAGE
COORD TIMEOUT:
HI-Z PHASE OC MIN
MESSAGE
PICKUP:
HI-Z NEUTRAL OC MIN
MESSAGE
PICKUP:
HI-Z PHASE RATE OF
MESSAGE
CHANGE: 150 A/2cycle
HI-Z NEUTRAL RATE OF
MESSAGE
CHANGE: 150 A/2cycle
F60 Feeder Protection System
See page 5–174.
See page 5–180.
See page 5–180.
See page 5–182.
See page 5–182.
See page 5–185.
See page 5–185.
HI-Z
Range: Disabled, Enabled
Range: SRC 1, SRC 2
Range: 1 to 10 in steps of 1
5
Range: 0.0 to 6000.0 s in steps of 0.1
Range: 10 to 250 in steps of 1
Range: 10 to 500 in steps of 1
Range: 5 to 180 min. in steps of 1
Range: 10 to 200 s in steps of 1
15 s
Range: 0.01 to 10.00 pu in steps of 0.01
1.50 pu
Range: 0.01 to 10.00 pu in steps of 0.01
1.00 pu
Range: 1 to 999 A/2cycle in steps of 1
Range: 1 to 999 A/2cycle in steps of 1
5 SETTINGS
5.6.11 MONITORING ELEMENTS
GE Multilin

Advertisement

Table of Contents
loading

Table of Contents