Flex State Parameters - GE UR Series F60 Instruction Manual

Feeder protection system
Hide thumbs Also See for UR Series F60:
Table of Contents

Advertisement

5 SETTINGS
The user-programmable pushbutton logic is shown below.
200
FLEXLOGIC OPERAND
msec
PUSHBUTTON 1 OFF
SETTING
PUSHBUTTON 1
FUNCTION
Disabled
Latched
OR
Self-Reset
SETTING
PUSHBTN 1 LOCAL
Off (FlexLogic operand)
SETTING
PUSHBTN 1 REMOTE
Off (FlexLogic operand)
SETTING
PUSHBTN 1 SET
Off (FlexLogic operand)
SETTING
PUSHBTN 1 RESET
Off (FlexLogic operand)
SETTING
SETTING
PUSHBTN 1 AUTORST
PUSHBTN 1 AUTORST
Disabled
DELAY
Enabled
t
PKP
200
FLEXLOGIC OPERAND
msec
PUSHBUTTON 1 ON
FLEXLOGIC OPERAND
PUSHBUTTON 1 ON
FLEXLOGIC OPERAND
PUSHBUTTON 2 ON
FLEXLOGIC OPERAND
OR
ANY PB ON
FLEXLOGIC OPERAND
PUSHBUTTON 3 ON
FLEXLOGIC OPERAND
*
INSTANTANEOUS RESET WILL BE EXECUTED IF ANY RELAY FRONT
PUSHBUTTON 12 ON
PANEL BUTTON IS PRESSED OR ANY NEW TARGET OR MESSAGE
BECOMES ACTIVE.
User-programmable pushbuttons require a type HP or HQ faceplate. If an HP or HQ type faceplate was ordered
separately, the relay order code must be changed to indicate the correct faceplate option. This can be done via
EnerVista UR Setup with the Maintenance > Enable Pushbutton command.
NOTE
PATH: SETTINGS
PRODUCT SETUP
FLEX STATE
PARAMETERS
MESSAGE
MESSAGE
GE Multilin
0
msec
Non Volatile Latch
50
msec
0
msec
OR
50
msec
0
msec
OR
OR
0
0
SETTING
msec
PUSH
PUSHBTN 1 DROP-OUT
TIME
0
OR
SETTING
PUSHBTN 1 MESSAGE
Disable
High Priority
Normal
Figure 5–9: USER-PROGRAMMABLE PUSHBUTTON LOGIC

FLEX STATE PARAMETERS

PARAMETER
1:
Off
PARAMETER
2:
Off
PARAMETER 256:
Off
F60 Feeder Protection System
OR
INSTANTANEOUS
RESET *
SET
LATCH
RST
FLEXLOGIC OPERAND
PUSHBUTTON 1 OFF
FLEXLOGIC OPERAND
PUSHBUTTON 1 ON
OR
THE MESSAGE IS TEMPORARILY REMOVED IF
ANY KEYPAD BUTTON IS PRESSED. TEN(10)
SECONDS OF KEYPAD INACTIVITY RESTORES
THE MESSAGE
see PRODUCT SETUP
> DISPLAY PROPERTIES menu
SETTING
FLASH MESSAGE
TIME
0
t RST
INSTANTANEOUS
RESET *
PUSHBUTTON 1 LED LOGIC
1. IF PUSHBUTTON 1 LED CONTROL IS SET TO OFF
FLEXLOGIC OPERAND
PUSHBUTTON 1 ON
2. IF PUSHBUTTON 1 LED CONTROL IS NOT SET TO OFF
SETTING
PUSHBTN 1 LED CTL
ANY FLEXLOGIC
OPERAND
5.2.15 FLEX STATE PARAMETERS
Range: FlexLogic™ operand
Range: FlexLogic™ operand
Range: FlexLogic™ operand
5.2 PRODUCT SETUP
see PRODUCT SETUP
> DISPLAY PROPERTIES menu
SETTING
FLASH MESSAGE
TIME
LCD MESSAGE
0
ENGAGE MESSAGE
t RST
SETTING
PUSHBTN 1 ID TEXT
XXXXXXXXXX
PUSHBTN 1 OFF TEXT
XXXXXXXXXX
OR
LCD MESSAGE
ENGAGE MESSAGE
t RST
SETTING
PUSHBTN 1 ID TEXT
XXXXXXXXXX
PUSHBTN 1 ON TEXT
XXXXXXXXXX
PB1
LED
PB1
LED
842021A1.DWG
5-49
5