1.6 Operating Authorization and Password
Controller provides multiple passwords and access management. According to different levels of passwords,
controller provides different levels of operating authorization. Details are as following:
Customer Password: factory set ____________
Permissions: Allows to modify all Customer Parameter
Factory Password: fixed ____________
Permissions: Allows user to modify all Parameter
2 Controller Function and Technical Parameter
Phase sequence protection:
When compressor is at stop mode an detects open phase, response time <2ms
Open phase protection
When any phase opens, the response time equals to set time: This fuinction is not activated when OPEN PHASE
PROTECTION time iss et over 20s
Motor protection: This control unit has the following 5 basic protection functions to the motor and fan.
o Rotor lock protection: After the starting oft he motor, if the working current reaches 4 or 8 times oft he set
value, the protection activates. The activate time is less than 0,2s.
o Short.circuit protection: If the detected current reaches 8times or more above the set value, the protection
activates, the activate time is less then 0,2s
o Lack phase protection: Any oft the phase lack, the protection activates and theactivate time ist he setting
time
o Unbalance protection: The current difference between any of the two phases reaches the percentage of the
setting value, the protection activates and the activate time is less than 5s.
o Protection features of overload, please see following table for your reference. Multiple=Iactual/Iset ,
response time is shown in following table according to overload multiples from 1.2 times an 3.0times.
I
/I
act
set
Time Para
response time (s)
04.08.2017
≥1.2
≥1.3
60
48
Operation Manual MAM - 200 V1.0
≥1.5
≥1.6
24
8
≥2.0
≥3.0
5
1
13