SCC MAM–200 Operation Manual page 11

Compressor controller
Table of Contents

Advertisement

BLOCK ON/OFF
TURN TIME
BLOCK NUMBER
BLOCK LOAD P
BLOCK UNLOAD P
BLOCK DELAY
OIL FILTER RESET
O/A RESET
Maintenance
parameter
AIR FILTER RESET
preset
LUB OIL RESET
LUB GREASE RESET
OIL FILTER
O/A SEPARATOR
Max. life time
AIR FILTER
preset
LUB. OIL
LUB GREASE
Language
display
User password
modification
04.08.2017
Alone/
Order
When master pressure is between BLOCK LOAD P and BLOCK UNLD P,
99 Hours
master determines slave to work alternatively after
working over this set time
0016
Number of air compressors in block net
In BLOCK mode, one compressor will start or load when master AIR P is
*.**MPa
below this set data
In BLOCK mode, one compressor will stop or unload when master AIR P is
*.**MPa
above this set Data
In BLOCK mode, when master sends two commands continuously, second
200S
command signal delays for this set data
Record total running time of OIL filter. If changing new oil filter, the data
0000 HOURS
should be reset by manual operation.
Record total running time of O/A filter. If changing new O/A separator, the
0000Hours
data should be reset by manual operation.
Record total running time of AIR filter. If changing new air filter, the data
0000Hours
should be reset by manual operation.
Record total running time of LUB OIL. If changing new lubricating oil, the
0000Hours
data should be reset by manual operation.
Record total running time of LUB GREASE. If changing new grease, the data
0000Hours
should be reset by manual operation.
1. Alarm prompt when total running time of oil filter is above the set data
9999Hours
2. Set this data to "0000", alarm function for
oil filter running time is not activated
1. Alarm prompt when total running time of O/A separator is above the set
data.
9999Hours
2. Set this data to "0000", alarm function for O/A separator running time is
not activated
1. Alarm prompt when total running time of air filter is above the set data.
9999Hours
2. Set this data to "0000", alarm function for air filter running time is not
activated
1. Alarm prompt when total running time of lubricant is above the set
data.
9999Hours
2. Set this data to "0000", alarm function for lubricant running time is not
activated.
1. Alarm prompt when total running time of grease is above the set data.
9999Hours
2. Set this data to "0" , alarm function for grease running time is not
activated
English
Change the display language.
User could modify the user password by old user password or factory
****
password
Operation Manual MAM - 200 V1.0
11