SCC MAM–200 Operation Manual page 12

Compressor controller
Table of Contents

Advertisement

1.5.3 Factory Parameter
The view and modification of factory parameter requires a factory password, The modification step is
same as customer parameter modification. Main function is as below:
Menu
HOST RATED CURRENT
FAN RATED CURRENT
PRE-ALARM T
STOP T
STOP P
UNLOAD P. UPPER LIMIT
LOAD TIME
TOTAL TIME
HISTORY FAULT RESET
UNBALANCE SCOPE
LACK PHASE PROTECTION
RUN MODE
04.08.2017
Initial Value Functions
After the starting delay time, when the motor current is greater than 1.2 times of the set
value and less than 4 times of the set value, the unit will jump as per overload feature.
Same as above
105℃
Pre-alarm when the temperature reaches this set value
110℃
Alarm when the air exhausting temperature reaches this set value.
1.00MPa
Alarm and stop the machine when the air supply temperature reaches this set value
0.80MPa
The Unload Limit Pressure in the Customer Parameter must be set lower than this value.
****Hours
Total load time
****Hours
Total run time
****
Input the history failure password to clear all the history failures.
When (the max. phase current / min. phase current) is greater than (1+set value), the
0006
unbalance protection will stop the machine. If the set value is greater than 15, the
unbalance protection will be unavailable.
0005
Set the LACK PHASE TIME ≥20S, the Lack phase protection will be disabled
VF
VF: Inverter will run
Commercial F
Commercial F: Star-delta will run
Operation Manual MAM - 200 V1.0