SCC MAM–200 Operation Manual page 10

Compressor controller
Table of Contents

Advertisement

1.5.2 Customer Parameter Table and Function
First
Second
Submenu
Submenu
LOADING P
UNLOAD P
FAN START
Set P / T / VF
FAN STOP
VF WORKING
RATED POWER
RATED SPEED
HOST START TIME
FAN START TIME
STAR DELAY TIME
LOAD DELAY TIME
SET TIME
EMPTY DELAY TIME
STOP DELAY TIME
START DELAY TIME
VSD UP SPEED
VSD DN SPEED
ON/OFF MODE
Operation mode
LOAD MODE
preset
COM MODE
COM ADRESS
Blocking
parameter
BLOCK STATE
preset
04.08.2017
Preset Value
Functions
1. In AUTO LOADING status, compressor will load if pressure is below this
set data
0,65 MPa
2. In STANDBY mode, compressor will start if the pressure below this set
data
1. Compressor will unload automatically if air pressure is above this set
data
0,80 MPa
2.This data should be set above LOADING P, also should be set below UNLD
P LIM
0080℃
Fan will start if AIR T is above this set data
0070℃
Fan will start if AIR T is above this set data
Set AIR P for VSD compressor to keep running stable, when pressure is
0,70MPa
fluctuated around this data, controller will adjust operation frequency of
inverter to control the pressure close to this data
015kW
Set RATED POWER in order to calculate actual power
Set RATED SPEED at 50HZ in order to calculate the actual speed in variable
2600RPM
frequency
Set the HOST START TIME. Record time when motor is activated, controller
0008s
will not start overload protection during this time to avoid impulse starting
current stopping the motor.
Set the FAN START TIME. Record time when fan is activated, controller will
0003s
not start overload protection during this time to avoid impulse starting
current stopping the fan
0006S
Interval time from star to delta
0002S
Unloading in this set time after enter delta running
When unloading continuously, compressor will automatically stop and
0600S
enter to standby status if over this set time
For NORMAL STOP operation, compressor will stop after it continuously
0010S
unloading over this set time
Machine cannot be restarted before this set time (stop and over time load
0100S
free stop till this time)
Restrict PID calculations in case the frequency increasing too fast which
0100
cause motor speeding up too fast
Restrict PID calculations in case the frequency decreasing too fast which
0100
cause motor slowing down too fast
NEAR: only the button on the controller can turn on and turn off the
machine.
Near / Far
FAR: both the button on the controller and
the remote-control button can turn on and turn off the machine;
Manual: Only when the pressure is above Unload P, compressor will
unload automatically. For any other case, the Load/Unload function can
Auto/
only be executed by pressing "load/unload" key.
Manual
AUTOMATICAL: the load/unload function can be executed by the
fluctuation of AIR P automatically
Prohibited: communication function is not activated.
Computer
COMPUTER: compressor can communicate with computer or DCS as slave
Block
according to MODBUS-RTU.
Prohibited
BLOCK: compressors can work in a net
0255
Communication address
1.When service as master in BLOCK, master
Main/
controls slave; the COM ADD should be set as No.1
2.When service as slave in BLOCK, slave is
Slave
controlled by master
Operation Manual MAM - 200 V1.0