Checking The Phase Current Operate Value, Pickup_Ph; Checking The Residual (Gf) Current Operate Value In> Set Below Ip; Checking The Re-Trip And Back-Up Times - ABB Relion 650 Series REL650 Commissioning Manual

Line distance protection, ansi
Table of Contents

Advertisement

1MRK 506 331-UUS A
6.4.10.1
6.4.10.2
6.4.10.3
Commissioning Manual
To verify the settings in the most common back-up trip mode 1 out of 3 it is sufficient
to test phase-to-ground-faults.
At mode 2 out of 4 the Phase current setting, Pickup_PH can be checked by single
phase injection where the return current is connected to the summed current input. The
value of residual (EF) current IN set lower than Pickup_PH is most easily checked in
backup trip mode 1 out of 4.

Checking the phase current operate value, Pickup_PH

Check the current level IP> where setting FunctionMode = Current and setting
BuTripMode = 1 out of 3 or 2 out of 4 as set under Main menu/Settings/IED Settings/
Current/CSPRBRF(50BF)/1:CSPRBRF.
1.
Apply the fault condition, including INITIATION of CSPRBRF (50BF), with a
current below set Pickup_PH.
2.
Repeat the fault condition and increase the current in steps until a trip occurs.
3.
Compare the result with the set Pickup_PH.
4.
Disconnect AC and INITIATE input signals.
If "No IPickup check" or "Retrip off" is set, only back-up trip can
be used to check set Pickup_PH.
Checking the residual (GF) current operate value
Check the low set IN> current where setting FunctionMode = Current and setting
BuTripMode = 1 out of 4 as set under Main menu/Settings/IED Settings/Current/
CSPRBRF(50BF)1:CSPRBRF.
1.
Apply the fault condition, including initiation of CSPRBRF 50BF, with a current
just below set Pickup_N.
2.
Repeat the fault condition and increase the current in steps until trip appears.
3.
Compare the result with the set Pickup_N.
4.
Disconnect AC and initiation input signals.

Checking the re-trip and back-up times

The check of the set times can be made in connection with the check of operate values
above. Choose the applicable function and trip mode, such as FunctionMode = Current
and setting RetripMode = No CBPos Check as set under Main menu/Settings/IED
Settings/CSPRBRF(50BF)/Current/1:CSPRBRF.
Section 6
Testing functionality
IN> set below IP>
81