ABB Relion 650 Series REL650 Commissioning Manual page 164

Line distance protection, ansi
Table of Contents

Advertisement

Section 8
Troubleshooting
156
2
1
GUID-31DF5495-91F1-4A4B-8FD5-50625038961E V1 EN
Figure 26:
Testing a trip contact
1 Trip contact under test
2 Current limiting resistor
To check the status of the output circuits driving the output relay via the LHMI,
select Main menu/Tests/Binary output values/Binary output modules and then
navigate to the board with the actual binary output to be checked.
Test and change the relay state manually.
1.
To set the IED to test mode, select Main menu/Tests/IED
testmode1:TESTMODE/TestMode and set the parameter to enable.
2.
To operate or force the output relay to operate, select and then navigate to
the board with the actual binary output relay to be operated/forced.
3.
Select the BOn_PO to be operated/forced and use
operate the actual output relay.
A
V
1MRK 506 331-UUS A
and
or
to
Commissioning Manual