Rosemount 648 Wireless
AMS
Suite: Intelligent Device Manager
When the device has joined the network, it will appear in the Device Manager as illustrated
below.
Troubleshooting
If the device is not joined to the network after power up, verify the correct configuration of the
Network ID and Join Key, and verify that Active Advertising has been enabled on the Smart
Wireless Gateway. The Network ID and Join Key in the device must match the Network ID
and Join Key of the Gateway.
The Network ID and Join Key may be obtained from the Smart Wireless Gateway on the
Setup>Network>Settings page on the web server (see Figure 4: Smart Wireless Gateway
Network Settings on page 7). The Network ID and Join Key may be changed in the wireless
device by using the following Fast Key sequence.
Function
Network
If the Field Communicator fails to communicate with the 648, open the LCD cover and verify
that the communication switch, located next to the LCD, is in the ON position. After this step,
verify that the 648 is communicating with the handheld device.
8
Key Sequence
1, 3, 3
Smart Power, Network ID, Set Join Key,